First commissioning
Connection of temperature sensor PT 100
8623-2 Example of connection to
8020 (Hall sensor)
3
3 (blue)
4
1
4 (black)
1 (brown)
Connection to (Hall sensor)
8020 (Pin 1) 8623-2 (M8, Pin 1 24 V DC output)
8020 (Pin 2) 8623-2 (M8, Pin 4 frequency input)
8020 (Pin 3) 8623-2 (M8, Pin 3 GND)
2
1
1 (brown)
3 (blue)
4 (black)
Bridge pin 1 and pin 4 of controller directly at the
senor PT100 and connect to pin 1 of PT100
Settings absolutely necessary onfirst commissioning
Type and range of standard signal (4 - 20 mA or 0 - 10 V)
with external setpoint
Lower limit for correcting variable
Do not connect a voltage to pin 1 of the 3-pole plug!
Pin1 is a 0.5 mA output to supply the senor (PT100)
Connection configuration of the controller types
8624-2 and 8625-2
M12, 4-pole
Supply voltage and
standard signal input
External setpoint
8624-2
M8, 3-pole
Standard
signal input
Sensor
M12 (4-pole):
Configuration
1 24 V DC supply voltage
2 Standard signal input, external setpoint
3 GND external setpoint
4 GND supply voltage
3
(blue)
2
(white)
4
(black)
1
(brown)*
M8 (3-polig):
4 (black)
1 (brown)
3 (blue)*
* wire colours when using
standards cables with
M8 Plug (3-pole).
8625-2
M8, 3-pole
PT 100 input
Configuration
Controller Pin 1(brown) Pin 3 (blue*) Pin 4 (black)
8623-2 24 V DC output GND Frequency input
(optionally needed
e.g. for Hall sensor)
8624-2 24 V DC output GND Standard signal
input, sensor
8625-2 PT 100 supply GND Temperature
(0.5 mA) input, PT 100
Connection configuration of the flow controller
type 8623-2
M12, 4-pole
supply voltage
and standard
signal input
external setpoint
M8, 3-pole
Sensor 1
M8, 3-pole
Sensor 2
(with ratio
control only)
Changing the cable outlet direction
Fig.:
Changing the cable outlet direction
Unscrew the 4 screws on the front of
the controller and remove the cover
carefully
Remove the screw to the valve and
remove the plastic cross.
Detach the plate from the cube.
Pull out the cube downwards and
replace in the desired orientation.
Place the plate onto the cube
(the pins must engage in the
guides.)
Lay on the plastic cross and insert
the screw through the cube.
Connect the controller to the
proportional valve.
pecialist
with the
roller and
the valve.
valve,
th the
ound
INSTALLATION / COMMISSIONING INSTALLATION / COMMISSIONING INSTALLATION / COMMISSIONING
In the case of controller, do not connect a voltage to
Pin 1 of the 3-pole plug!
Pin 1 is a output for supply of the sensors.